Relé Térmico 36-45A S2 - 3RU2136-4GB0 - Siemens
SKU 3RU2136-4GB0 · Unidad base: unit
Producto Siemens. Referencia del fabricante: 3RU2136-4GB0. Overload relay 36...45 A Thermal For motor protection Size S2, Class 10 Contactor mounting Main circuit: Screw Auxiliary circuit: Screw Manual-Automatic-Reset Características técnicas: product designation: thermal overload relay; product type designation: 3RU2; size of overload relay: S2; size of contactor can be combined company-specific: S2; power loss [W] for rated value of the current at AC in hot operating state: 15.6 W; ● per pole: 5.2 W; type of calculation of power loss current-dependent: quadratic; insulation voltage with degree of pollution 3 at AC rated value: 690 V; surge voltage resistance rated value: 6 kV; ● in networks with ungrounded star point between auxiliary and auxiliary circuit: 415 V; ● in networks with grounded star point between auxiliary and auxiliary circuit: 415 V; ● in networks with ungrounded star point between main and auxiliary circuit: 690 V.
Ingresa o regístrate para consultar el stock registrado.
Ingresar ↗La solicitud no reserva mercadería ni confirma un pedido.
Consultar ficha técnica ↗Características del producto
- product designation
- thermal overload relay
- product type designation
- 3RU2
- size of overload relay
- S2
- size of contactor can be combined company-specific
- S2
- power loss [W] for rated value of the current at AC in hot operating state
- 15.6 W
- ● per pole
- 5.2 W
- type of calculation of power loss current-dependent
- quadratic
- insulation voltage with degree of pollution 3 at AC rated value
- 690 V
- surge voltage resistance rated value
- 6 kV
- ● in networks with ungrounded star point between auxiliary and auxiliary circuit
- 415 V
- ● in networks with grounded star point between auxiliary and auxiliary circuit
- 415 V
- ● in networks with ungrounded star point between main and auxiliary circuit
- 690 V
- ● in networks with grounded star point between main and auxiliary circuit
- 690 V
- shock resistance according to IEC 60068-2-27
- 8g / 11 ms
- ● with automatic reset typical
- 10 min
- ● with remote-reset
- 10 min
- ● with manual reset
- 10 min
- reference code according to IEC 81346-2
- F
- Substance Prohibitance (day/month/year)
- 10/15/2014
- Net Weight
- 301.8 g
- installation altitude at height above sea level maximum
- 2 000 m
- ● during operation
- -40 ... +70 °C
- ● during storage
- -55 ... +80 °C
- ● during transport
- -55 ... +80 °C
- temperature compensation
- -40 ... +60 °C
- relative humidity during operation
- 10 ... 95 %
- number of poles for main current circuit
- 3
- adjustable current response value current of the current-dependent overload release
- 36 ... 45 A
- ● rated value
- 690 V
- ● at AC-3e rated value maximum
- 690 V
- operating frequency rated value
- 50 ... 60 Hz
- operational current rated value
- 45 A
- operational current at AC-3e at 400 V rated value
- 45 A
- — at 400 V rated value
- 22 kW
- — at 500 V rated value
- 30 kW
- — at 690 V rated value
- 37 kW
- design of the auxiliary switch
- integrated
- number of NC contacts for auxiliary contacts
- 1
- ● note
- for contactor disconnection
- number of NO contacts for auxiliary contacts
- 1
- number of CO contacts for auxiliary contacts
- 0
- ● at 24 V
- 3 A
- ● at 110 V
- 3 A
- ● at 120 V
- 3 A
- ● at 125 V
- 3 A
- ● at 230 V
- 2 A
- ● at 400 V
- 1 A
- ● at 690 V
- 0.75 A
- ● at 60 V
- 0.3 A
- ● at 220 V
- 0.11 A
- design of the miniature circuit breaker for short-circuit protection of the auxiliary switch required
- 6A (SCC less than equal to 0.5 kA; U less than equal to 260V)
- contact rating of auxiliary contacts according to UL
- B600 / R300
- trip class
- CLASS 10
- design of the overload release
- thermal
- ● at 480 V rated value
- 45 A
- ● at 600 V rated value
- 45 A
- ● for short-circuit protection of the auxiliary switch required
- fuse gG: 6 A, quick: 10 A
- mounting position
- for mounting on contactors: with a vertical mounting plane +/-135° rotatable & +/- 22.5° tiltable, stand-alone installation: with a vertical mounting plane +/-135° rotatable and +/-45° tiltable; for more details see manual
- fastening method
- Contactor mounting
- height
- 90 mm