Materiales eléctricos · Piura, PerúAtención a empresas y profesionales
Mi lista 0
SIEMENS Guardamotor Automático S2 35-45A - 3RV2031-4VA10 - Siemens 3RV2031-4VA10
SIEMENS

Guardamotor Automático S2 35-45A - 3RV2031-4VA10 - Siemens

SKU 3RV2031-4VA10 · Unidad base: unit

Producto Siemens. Referencia del fabricante: 3RV2031-4VA10. Circuit breaker size S2 for motor protection, CLASS 10 A-release 35...45 A N-release 650 A screw terminal Standard switching capacity Características técnicas: product designation: Circuit breaker; design of the product: For motor protection; product type designation: 3RV2; Product equipment of circuit breaker for motor protection complete unit with protection device: Yes; size of the circuit-breaker: S2; size of contactor can be combined company-specific: S2; product function disconnector functionality: Yes; product extension auxiliary switch: Yes; ● at AC in hot operating state: 24.5 W; ● at AC in hot operating state per pole: 8.2 W; type of calculation of power loss current-dependent: quadratic; insulation voltage with degree of pollution 3 at AC rated value: 690 V.

Consulta existencias con tu cuenta.

Ingresa o regístrate para consultar el stock registrado.

Ingresar ↗

La solicitud no reserva mercadería ni confirma un pedido.

Consultar ficha técnica ↗

Características del producto

product designation
Circuit breaker
design of the product
For motor protection
product type designation
3RV2
Product equipment of circuit breaker for motor protection complete unit with protection device
Yes
size of the circuit-breaker
S2
size of contactor can be combined company-specific
S2
product function disconnector functionality
Yes
product extension auxiliary switch
Yes
● at AC in hot operating state
24.5 W
● at AC in hot operating state per pole
8.2 W
type of calculation of power loss current-dependent
quadratic
insulation voltage with degree of pollution 3 at AC rated value
690 V
surge voltage resistance rated value
6 kV
● in networks with ungrounded star point between main and auxiliary circuit
400 V
● in networks with grounded star point between main and auxiliary circuit
400 V
● on the front according to IEC 60529
IP20
● on the front
IP20
● of the terminal
IP00
shock resistance according to IEC 60068-2-27
25 g / 11 ms Sinus
● of the main contacts typical
50 000
● of auxiliary contacts typical
50 000
electrical endurance (operating cycles) typical
50 000
reference code according to IEC 81346-2
Q
continuous current rated value
45 A
Substance Prohibitance (day/month/year)
10/15/2014
SVHC substance name
Lead CAS-No. 7439-92-1
Net Weight
1.068 kg
installation altitude at height above sea level maximum
2 000 m
● during operation
-20 ... +60 °C
● during storage
-50 ... +80 °C
● during transport
-50 ... +80 °C
temperature compensation
-20 ... +60 °C
relative humidity during operation
10 ... 95 %
number of poles for main current circuit
3
adjustable current response value current of the current-dependent overload release
35 ... 45 A
type of voltage for main current circuit
AC
● rated value
690 V
● at AC-3 rated value maximum
690 V
● at AC-3e rated value maximum
690 V
operating frequency rated value
50 ... 60 Hz
operational current rated value
45 A
● at AC-3 at 400 V rated value
45 A
● at AC-3e at 400 V rated value
45 A
— at 230 V rated value
11 kW
— at 400 V rated value
22 kW
— at 500 V rated value
30 kW
— at 690 V rated value
37 kW
● at AC-3 maximum
15 1/h
● at AC-3e maximum
15 1/h
type of voltage for auxiliary and control circuit
AC/DC
number of NC contacts for auxiliary contacts
0
number of NO contacts for auxiliary contacts
0
number of CO contacts for auxiliary contacts
0
● ground fault detection
No
● phase failure detection
Yes
trip class
CLASS 10
design of the overload release
thermal
protection function thermal overload protection (ANSI 49)
Yes
● at AC at 240 V rated value
100 kA
● at AC at 400 V rated value
65 kA
WhatsApp