Relé Digital Falla Perdida Fase/Secuencia /Desbalance De Fase,minima Y Maxima Tensión, 3 X 160 - 690 Vac, 1NA+ 1NC 3UG4615-1CR20 - Siemens
SKU 3UG4615-1CR20 · Unidad base: unit
Producto Siemens. Referencia del fabricante: 3UG4615-1CR20. !!! product phase-out !!! the preferred successor is 3UG5616-1CR20 phase failure and sequence monitoring 3x 160-690 V, screw terminal digital monitoring relay for 3-phase line voltage connectable phase sequence phase failure 3 x 160 to 690 V 50 to 60 Hz AC undervoltage and overvoltage 160-690 V hysteresis 1-20 V 0-20 s each for Umin and Umax 1 changeover contact for Umin 1 changeover contact for Umax screw terminal Características técnicas: product designation: Network monitoring relay with digital setting; design of the product: 5 functions; product type designation: 3UG4; product function: Phase monitoring relay; display version LED: No; design of the display: LCD; ● with degree of pollution 3 rated value: 690 V; degree of pollution: 3; ● for monitoring: AC; surge voltage resistance rated value: 6 kV; shock resistance according to IEC 60068-2-27: sinusoidal half-wave 15 g / 11 ms; vibration resistance according to IEC 60068-2-6: 1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2 g.
Ingresa o regístrate para consultar el stock registrado.
Ingresar ↗La solicitud no reserva mercadería ni confirma un pedido.
Consultar ficha técnica ↗Características del producto
- product designation
- Network monitoring relay with digital setting
- design of the product
- 5 functions
- product type designation
- 3UG4
- product function
- Phase monitoring relay
- display version LED
- No
- design of the display
- LCD
- ● with degree of pollution 3 rated value
- 690 V
- degree of pollution
- 3
- ● for monitoring
- AC
- surge voltage resistance rated value
- 6 kV
- shock resistance according to IEC 60068-2-27
- sinusoidal half-wave 15 g / 11 ms
- vibration resistance according to IEC 60068-2-6
- 1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2 g
- mechanical service life (operating cycles) typical
- 10 000 000
- electrical endurance (operating cycles) at AC-15 at 230 V typical
- 100 000
- thermal current of the switching element with contacts maximum
- 5 A
- reference code according to IEC 81346-2
- K
- relative repeat accuracy
- 1 %
- Substance Prohibitance (day/month/year)
- 05/01/2012
- SVHC substance name
- Lead CAS-No. 7439-92-1 Lead monoxide (lead oxide) CAS-No. 1317-36-8 2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one CAS-No. 71868-10-5 Melamine CAS-No. 108-78-1 6,6'-di-tert-butyl-2,2'-methylenedi-p-cresol CAS-No. 119-47-1
- Net Weight
- 130.58 g
- ● undervoltage detection
- Yes
- ● overvoltage detection
- Yes
- ● phase sequence recognition
- Yes
- ● phase failure detection
- Yes
- ● asymmetry detection
- Yes; not adjustable, indirectly by monitoring the voltage limit values
- ● overcurrent detection 1 phase
- No
- ● overvoltage detection 3 phase
- Yes
- ● undercurrent detection 1 phase
- No
- ● undervoltage detection 3 phases
- Yes
- ● voltage window recognition 3 phase
- Yes
- ● adjustable open/closed-circuit current principle
- Yes
- ● auto-RESET
- Yes
- type of voltage of the control supply voltage
- AC
- ● initial value
- 1
- ● full-scale value
- 1
- design of the interface bluetooth
- No
- ● with lower or upper limit violation
- 0.1 ... 20 s
- response time maximum
- 450 ms
- accuracy of digital display
- +/-1 digit
- relative metering precision
- 5 %
- number of NC contacts delayed switching
- 0
- number of NO contacts delayed switching
- 0
- ● for auxiliary contacts
- 2
- ● delayed switching
- 2
- operating frequency with 3RT2 contactor maximum
- 5 000 1/h
- number of poles for main current circuit
- 3
- ● at 250 V at 50/60 Hz
- 3 A
- ● at 400 V at 50/60 Hz
- 3 A
- ● at 24 V
- 1 A
- ● at 125 V
- 0 A
- ● at 250 V
- 0 A
- operational current at 17 V minimum
- 5 mA
- continuous current of the DIAZED fuse link of the output relay
- 4 A
- ● due to burst according to IEC 61000-4-4
- 2 kV
- ● due to conductor-earth surge according to IEC 61000-4-5
- 2 kV
- ● due to conductor-conductor surge according to IEC 61000-4-5
- 1 kV
- field-based interference according to IEC 61000-4-3
- 10 V/m
- electrostatic discharge according to IEC 61000-4-2
- 6 kV contact discharge / 8 kV air discharge
- ● between input and output
- Yes
- ● between the outputs
- Yes