Materiales eléctricos · Piura, PerúAtención a empresas y profesionales
Mi lista 0
SIEMENS Relé Digital Falla Perdida Fase/Secuencia /Desbalance De Fase,minima Y Maxima Tensión, 3 X 160 - 690 Vac, 1NA+ 1NC 3UG4615-1CR20 - Siemens 3UG4615-1CR20
SIEMENS

Relé Digital Falla Perdida Fase/Secuencia /Desbalance De Fase,minima Y Maxima Tensión, 3 X 160 - 690 Vac, 1NA+ 1NC 3UG4615-1CR20 - Siemens

SKU 3UG4615-1CR20 · Unidad base: unit

Producto Siemens. Referencia del fabricante: 3UG4615-1CR20. !!! product phase-out !!! the preferred successor is 3UG5616-1CR20 phase failure and sequence monitoring 3x 160-690 V, screw terminal digital monitoring relay for 3-phase line voltage connectable phase sequence phase failure 3 x 160 to 690 V 50 to 60 Hz AC undervoltage and overvoltage 160-690 V hysteresis 1-20 V 0-20 s each for Umin and Umax 1 changeover contact for Umin 1 changeover contact for Umax screw terminal Características técnicas: product designation: Network monitoring relay with digital setting; design of the product: 5 functions; product type designation: 3UG4; product function: Phase monitoring relay; display version LED: No; design of the display: LCD; ● with degree of pollution 3 rated value: 690 V; degree of pollution: 3; ● for monitoring: AC; surge voltage resistance rated value: 6 kV; shock resistance according to IEC 60068-2-27: sinusoidal half-wave 15 g / 11 ms; vibration resistance according to IEC 60068-2-6: 1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2 g.

Consulta existencias con tu cuenta.

Ingresa o regístrate para consultar el stock registrado.

Ingresar ↗

La solicitud no reserva mercadería ni confirma un pedido.

Consultar ficha técnica ↗

Características del producto

product designation
Network monitoring relay with digital setting
design of the product
5 functions
product type designation
3UG4
product function
Phase monitoring relay
display version LED
No
design of the display
LCD
● with degree of pollution 3 rated value
690 V
degree of pollution
3
● for monitoring
AC
surge voltage resistance rated value
6 kV
shock resistance according to IEC 60068-2-27
sinusoidal half-wave 15 g / 11 ms
vibration resistance according to IEC 60068-2-6
1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2 g
mechanical service life (operating cycles) typical
10 000 000
electrical endurance (operating cycles) at AC-15 at 230 V typical
100 000
thermal current of the switching element with contacts maximum
5 A
reference code according to IEC 81346-2
K
relative repeat accuracy
1 %
Substance Prohibitance (day/month/year)
05/01/2012
SVHC substance name
Lead CAS-No. 7439-92-1 Lead monoxide (lead oxide) CAS-No. 1317-36-8 2-methyl-1-(4-methylthiophenyl)-2-morpholinopropan-1-one CAS-No. 71868-10-5 Melamine CAS-No. 108-78-1 6,6'-di-tert-butyl-2,2'-methylenedi-p-cresol CAS-No. 119-47-1
Net Weight
130.58 g
● undervoltage detection
Yes
● overvoltage detection
Yes
● phase sequence recognition
Yes
● phase failure detection
Yes
● asymmetry detection
Yes; not adjustable, indirectly by monitoring the voltage limit values
● overcurrent detection 1 phase
No
● overvoltage detection 3 phase
Yes
● undercurrent detection 1 phase
No
● undervoltage detection 3 phases
Yes
● voltage window recognition 3 phase
Yes
● adjustable open/closed-circuit current principle
Yes
● auto-RESET
Yes
type of voltage of the control supply voltage
AC
● initial value
1
● full-scale value
1
design of the interface bluetooth
No
● with lower or upper limit violation
0.1 ... 20 s
response time maximum
450 ms
accuracy of digital display
+/-1 digit
relative metering precision
5 %
number of NC contacts delayed switching
0
number of NO contacts delayed switching
0
● for auxiliary contacts
2
● delayed switching
2
operating frequency with 3RT2 contactor maximum
5 000 1/h
number of poles for main current circuit
3
● at 250 V at 50/60 Hz
3 A
● at 400 V at 50/60 Hz
3 A
● at 24 V
1 A
● at 125 V
0 A
● at 250 V
0 A
operational current at 17 V minimum
5 mA
continuous current of the DIAZED fuse link of the output relay
4 A
● due to burst according to IEC 61000-4-4
2 kV
● due to conductor-earth surge according to IEC 61000-4-5
2 kV
● due to conductor-conductor surge according to IEC 61000-4-5
1 kV
field-based interference according to IEC 61000-4-3
10 V/m
electrostatic discharge according to IEC 61000-4-2
6 kV contact discharge / 8 kV air discharge
● between input and output
Yes
● between the outputs
Yes
WhatsApp