Materiales eléctricos · Piura, PerúAtención a empresas y profesionales
Mi lista 0
SIEMENS Interruptor Termomagnetico 160-400 A ICU=85KA @ 220V 3VM1 3VA2340-5HL32-0AA0 - Siemens 3VA23405HL32
SIEMENS

Interruptor Termomagnetico 160-400 A ICU=85KA @ 220V 3VM1 3VA2340-5HL32-0AA0 - Siemens

SKU 3VA23405HL32 · Unidad base: unit

Producto Siemens. Referencia del fabricante: 3VA2340-5HL32-0AA0. circuit breaker 3VA2 IEC Frame 400 breaking capacity class M Icu=55 kA @ 415 V 3-pole, line protection ETU320, LI, In=400 A overload protection Ir=160 A...400 A short-circuit protection Ii=1.5...10 x In nut keeper kit Características técnicas: product designation: Molded case circuit breaker; design of the product: Line protection; design of the overcurrent release: ETU320; protection function of the overcurrent release: LI; number of poles: 3; insulation voltage / rated value: 800 V; operating voltage / at AC / rated value: 690 V; power loss [W] / maximum: 96 W; power loss [W] / for rated value of the current / at AC / in hot operating state / per pole: 32 W; mechanical service life (operating cycles) / typical: 20 000; electrical endurance (operating cycles) / at AC-1 / at 380/415 V: 6 000; electrical endurance (operating cycles) / at AC-1 / at 690 V: 4 200.

Consulta existencias con tu cuenta.

Ingresa o regístrate para consultar el stock registrado.

Ingresar ↗

La solicitud no reserva mercadería ni confirma un pedido.

Consultar ficha técnica ↗

Características del producto

product designation
Molded case circuit breaker
design of the product
Line protection
design of the overcurrent release
ETU320
protection function of the overcurrent release
LI
number of poles
3
insulation voltage / rated value
800 V
operating voltage / at AC / rated value
690 V
power loss [W] / maximum
96 W
power loss [W] / for rated value of the current / at AC / in hot operating state / per pole
32 W
mechanical service life (operating cycles) / typical
20 000
electrical endurance (operating cycles) / at AC-1 / at 380/415 V
6 000
electrical endurance (operating cycles) / at AC-1 / at 690 V
4 200
product feature / for neutral conductors / upgradable/retrofittable / short-circuit and overload proof
No
ground-fault monitoring version
Without
● communication function
No
● other measurement function
No
Net Weight
4.619 kg
● at 40 °C
400 A
● at 45 °C
400 A
● at 50 °C
400 A
● at 55 °C
385 A
● at 60 °C
370 A
● at 65 °C
355 A
● at 70 °C
340 A
switching capacity class of the circuit breaker
M
● at 240 V
85 kA
● at 415 V
55 kA
● at 440 V
55 kA
● at 500 V
36 kA
● at 690 V
5 kA
product feature / for L-tripping / can be switched on/off
No
● minimum
160 A
● maximum
400 A
product function / grounding protection
No
● undervoltage release
No
● voltage trigger
No
● trip indicator
No
height [in]
9.76 in
height
248 mm
width [in]
5.43 in
width
138 mm
depth [in]
4.33 in
depth
110 mm
arrangement of electrical connectors / for main current circuit
Front terminal
type of electrical connection / for main current circuit
on both sides nut keeper kit
type of connectable conductor cross-sections / for flat-bar terminal connection / minimum
20 x 1 mm
type of connectable conductor cross-sections / for flat-bar terminal connection / maximum
35 x 10 mm
design of the surface / of the connections / on the top of the switch (N, 1, 3, 5)
silver
design of the surface / of the connections / on the bottom of the switch (N, 2, 4, 6)
silver
number of CO contacts / for auxiliary contacts
0
product extension / optional / motor drive
Yes
protection class IP / on the front
IP40
● during operation / minimum
-25 °C
● during operation / maximum
70 °C
● during storage / minimum
-40 °C
● during storage / maximum
80 °C
global warming potential [CO2 eq] / total
495 kg
global warming potential [CO2 eq] / during manufacturing
28.7 kg
global warming potential [CO2 eq] / during operation
470 kg
global warming potential [CO2 eq] / after end of life
-4.07 kg
WhatsApp