Materiales eléctricos · Piura, PerúAtención a empresas y profesionales
Mi lista 0
SIEMENS Fuente De Alimentacion Estabilizada Entrada 120-230VAC Salida 24VDC 10A Con Interfaz De Diagnostico 6EP3334-7SB00-3AX0 6EP3334-7SB00-3AX0
SIEMENS

Fuente De Alimentacion Estabilizada Entrada 120-230VAC Salida 24VDC 10A Con Interfaz De Diagnostico 6EP3334-7SB00-3AX0

SKU 6EP3334-7SB00-3AX0 · Unidad base: unit

Producto Siemens. Referencia del fabricante: 6EP3334-7SB00-3AX0. SITOP PSU6200/1AC/24VDC/10A SITOP PSU6200 24 V/10 A stabilized power supply input: 120 - 240 V AC (110 - 240 V DC) output: 24 V DC/10 A with diagnostic interface Características técnicas: Technical Product Detail Page: https://i.siemens.com/1P6EP3334-7SB00-3AX0; product type designation: PSU6200; product designation: Power supply SITOP PSU6200; type of current supply: 24 V/10 A; type of the power supply network: 1-phase AC or DC; phase number: 1; voltage curve at input: AC/DC; ● minimum rated value: 120 V; ● maximum rated value: 240 V; ● initial value: 85 V; ● full-scale value: 264 V; supply voltage at DC: 110 ... 240 V.

Consulta existencias con tu cuenta.

Ingresa o regístrate para consultar el stock registrado.

Ingresar ↗

La solicitud no reserva mercadería ni confirma un pedido.

Consultar ficha técnica ↗

Características del producto

Technical Product Detail Page
https://i.siemens.com/1P6EP3334-7SB00-3AX0
product type designation
PSU6200
product designation
Power supply SITOP PSU6200
type of current supply
24 V/10 A
type of the power supply network
1-phase AC or DC
phase number
1
voltage curve at input
AC/DC
● minimum rated value
120 V
● maximum rated value
240 V
● initial value
85 V
● full-scale value
264 V
supply voltage at DC
110 ... 240 V
input voltage at DC
85 ... 275 V
● at 50 Hz
240 V
● at 60 Hz
120 V
line frequency
50/60 Hz
wide range input
Yes
overvoltage overload capability
300 V AC for 30 s
buffering time for rated value of the output current in the event of power failure minimum
45 ms
operating condition of the mains buffering
at Vin = 240 V
● at rated input voltage 120 V
2.2 A
● at rated input voltage 240 V
1.2 A
current limitation of inrush current at 25 °C maximum
6 A
fuse protection type
5 A
fuse protection type in the feeder
Circuit breaker from 4 A characteristic C/6 A characteristic B to 10 A characteristic C or circuit breaker 3RV2011-1EA10 (setting 4 A) or 3RV2711-1ED10 (UL 489)
voltage curve at output
Controlled, isolated DC voltage
product function output voltage controlled
Yes
product function output voltage stabilized
Yes
number of outputs
1
output voltage at DC rated value
24 V
● at output 1 at DC rated value
24 V
● at output 1 at DC
24 V
output voltage adjustable
Yes; via potentiometer
adjustable output voltage
24 ... 28 V; max. 240 W (288 W up to 45°C)
relative overall tolerance of the voltage
3 %
● on slow fluctuation of input voltage
0.1 %
● on slow fluctuation of ohm loading
0.1 %
● maximum
30 mV
● typical
20 mV
display version for normal operation
Green LED for 24 V OK
type of signal at output
Electronic contact (NO contact, contact rating 30 V DC/0.1 A) for DC O.K. or diagnostic interface
behavior of the output voltage when switching on
Overshoot of Vout < 2 %
response delay maximum
0.5 s
● rated value
10 A
● rated range
0 ... 10 A; 12 A up to +45°C; +60 ... +70 °C: Derating 3%/K
supplied active power typical
240 W
● on short-circuiting during the start-up typical
12 A
● at short-circuit during operation typical
12 A
parallel switching of outputs
can be set with DIP switch
bridging of equipment
Yes; switchable characteristic
number of parallel-switched equipment resources for increasing the power
2
efficiency in percent
92.8 %
● at rated output voltage for rated value of the output current typical
18 W
● during no-load operation maximum
2.2 W
relative control precision of the output voltage at load step of resistive load 10/90/10 % typical
2 %
● load step 10 to 90% typical
2 ms
● load step 90 to 10% typical
2 ms
design of the overvoltage protection
< 32 V
property of the output short-circuit proof
Yes
design of short-circuit protection
Shutdown and periodic restart attempts