Sentron, PAC4200, Lcd, 200 Variables 7KM4212-0BA00-3AA0 - Siemens
SKU 7KM4212-0BA00-3AA0 · Unidad base: unit
Producto Siemens. Referencia del fabricante: 7KM4212-0BA00-3AA0. SENTRON, measuring device, 7KM PAC4200, LCD, L-L: 690 V, L-N: 400 V, 5 A, 3-phase, Modbus TCP, optionally Modbus RTU / PROFINET / PROFIBUS / DI/DQ, apparent / active / reactive energy / cos phi, harmonics: 2nd - 64th, THD, Class 0.2 acc. to IEC 61557-12 or Class 0.2 s acc. to IEC 62053-22, wide-range power supply 95 to 240 V +-10% (AC), 110 to 340 V +-10% (DC) screw terminals Características técnicas: product designation: Measuring device for power system quality measurement; design of the product: compact; product type designation: 7KM PAC4200; ● for voltage measurement: TRMS; ● for current measurement: TRMS; type of measured value detection: complete; voltage curve: Sinusoidal or distorted; ● initial value: 45 Hz; ● full-scale value: 65 Hz; operating mode for measured value detection automatic line frequency detection: Yes; ● set at 50 Hz: No; ● set to 60 Hz: No.
Ingresa o regístrate para consultar el stock registrado.
Ingresar ↗La solicitud no reserva mercadería ni confirma un pedido.
Consultar ficha técnica ↗Características del producto
- product designation
- Measuring device for power system quality measurement
- design of the product
- compact
- product type designation
- 7KM PAC4200
- ● for voltage measurement
- TRMS
- ● for current measurement
- TRMS
- type of measured value detection
- complete
- voltage curve
- Sinusoidal or distorted
- ● initial value
- 45 Hz
- ● full-scale value
- 65 Hz
- operating mode for measured value detection automatic line frequency detection
- Yes
- ● set at 50 Hz
- No
- ● set to 60 Hz
- No
- design of the power supply
- Wide-range power supply
- type of voltage of the supply voltage
- AC/DC
- supply voltage at AC
- 95 ... 240 V
- supply voltage at DC
- 110 ... 340 V
- protection class IP on the front
- IP65
- operating resource protection class when installed
- II
- suitability for operation
- Installation in stationary panels in closed rooms
- ● voltage measurement
- Yes
- ● current measurement
- Yes
- ● active power measurement
- Yes
- ● reactive power measurement
- Yes
- ● frequency measurement
- Yes
- design of the display
- LCD
- height of the display
- 54 mm
- width of the display
- 72 mm
- color of the background of the display
- white
- illuminance of display backlight adjustable
- Yes
- time-controlled reduction of the illuminance of display backlight possible
- Yes
- display contrast adjustable
- Yes
- national language on the display screen is supported
- ger, en, fr, spa, ita, por, tur, rus, chi, pol
- number of keys
- 4
- transfer rate minimum
- 10 000 kbit/s
- transfer rate maximum
- 100 000 kbit/s
- number of interfaces according to Fast Ethernet
- 1
- type of electrical connection of the fast Ethernet interface
- RJ45 (8P8C)
- protocol at the Ethernet interface is supported
- MODBUS TCP
- transfer rate 1 for Ethernet
- 10 Mbit/s
- transfer rate 2 for Ethernet
- 100 Mbit/s
- reference condition for metering accuracy
- according to IEC61557-12
- ● for measured variable voltage
- +/- 0.2 %
- ● for measured variable current
- +/- 0.2 %
- ● for measured variable output factor
- +/- 2 %
- ● for measured variable active energy
- Class 0.2 according to IEC61557-12 and/or class 0.2S according to IEC62053-22
- ● for measured variable reactive energy
- Class 2 according to IEC61557-12 and/or IEC62053-23
- ● for measured variable THD
- +/- 2 %
- number of digital inputs
- 2
- type of electrical connection at the digital inputs
- screw-type terminals
- operating conditions for digital inputs external voltage supply
- Yes
- input voltage at digital input at DC maximum
- 30 V
- number of digital outputs
- 2
- type of switching output
- solid state
- digital output version
- switching or pulse output function
- operating voltage as output voltage at DC maximum permissible
- 30 V
- type of electrical connection at the digital outputs
- screw-type terminals
- ● at digital output with signal maximum
- 0.2 mA
- ● at digital output for signal maximum
- 27 mA
- ● at the digital outputs at DC limited to 100 ms maximum
- 300 mA
- internal resistance at the digital outputs
- 55 Ω